Litco SystemsAlpha4 FAQ

FAQ INDEX

Additional information is often added to this section so please check back frequently.

1.1 ABOUT ALPHA4 "V" DEVICE

1.2 WHY MUST ALPHA4 BE CONNECTED DIRECTLY TO THE BATTERY?

1.3 WHAT TO DO IF YOU DO NOT KNOW CAPACITY OF YOUR BATTERY

1.4 WHAT TO DO IF YOU OBTAIN "V.LO" MESSAGE ON ANY OF THE DEVICES.

1.5 UNDER WHAT CONDITIONS SHOULD 18 GAUGE 36 INCH ADAPTER CABLE BE USED?

1.6 CAN I CHARGE AND CYCLE RAYOVAC RENEWAL CELLS ON THE ALPHA4?

1.7 WHAT ALPHA4 DEVICES SHOULD I USE FOR CYCLING AND CHARGING NIMH BATTERIES?

1.8
WILL REVERSE PULSING OR "BURP" CHARGING REJUVENATE MY BATTERY?

1.9
WHY CAN CHARGERS USING TIMERS DAMAGE BATTERIES?

2.0 USING "N" DEVICE WITH NEW NICADS

2.1 WILL ALPHA4 CHARGE LITHIUM BATTERIES?

2.2 IS MEASURING INPUT CAPACITY DURING CHARGING OF VALUE?

2.3 WHAT FAST CHARGE CURRENTS ARE RECOMMENDED FOR FAST CHARGING TX AND RX.

2.4 ADDITIONAL INFORMATION ABOUT USE OF ALPHA4 "I", "A" AND "V" DEVICES.

2.5 ABOUT CHARGING WET AND GEL CELLS

2.6 TESTING ADAPTER CABLES WITH ALPHA4

2.7 WILL CONTINUOUS TRICKLE CHARGING HURT BATTERIES?

2.8 BATTERY CAPACITY MEASUREMENTS

2.9 SURFACE CHARGE VS ACCEPTED CHARGE.

Go to Alpha4 index page . .

1.1

ABOUT ALPHA4 "V" DEVICE

As a rule most ESV's other than "V" device on A4 have a very small load such as 100 mA, which is almost the same as no load at all. This is because they cannot handle the power dissipation that a large load such as 1000 mA on A4 will dissipate. For this reason the voltage reading on these ESV's will be close to noload reading on A4. The large load of 1000 mA is necessary because if a servo stalls due to jamming or high air load it will typically draw stall current of about 1000 mA. The 1000 mA load of the A4 "V" device is not constant but pulsed. The load voltage reading is taken during the 1000 mA load pulse. The average current is only about 150 mA depending on how many ports are programmed. This high load not only allows for testing batteries but also connectors and switches.

The pins in a typical connector are crimped to a stranded copper wire that is not normally solder plated. In time corrosion develops at the joint causing higher than normal resistance which results in excessive voltage drop across the joint. This results in lower than normal voltage to be available to the rest of the airborne system which could cause a failure. This failure would most likely occur during periods of high current load such as when the aircraft is diving and up elevator is applied. This high air load on the servo could result in a servo stall condition and high current draw.

Using the "V" device
The A4 instruction manual explains the use of "V" device under the heading: "PROGRAMMING VOLTMETER ("V" ON THE KEYPAD).

First program a Voltmeter ("V") on one of the ports and connect battery to be tested to that port. Next press and HOLD a key on the keypad that corresponds to the number of cells in the battery that you are testing. If the battery has 4 cells then press and HOLD key "4". If there is no message on the screen the battery is OK. If V.LO flashes the battery fails under load ( the battery is below 4.72 V if the pack has 4 cells). If V.LO is steady the battery fails under both load and noload.

Note that A4 allows the battery to go to 1.18V per cell under 1000 mA load before flashing V.LO warning message. With typical ESV you would normally go down to 1.175 V per cell under very light load (100mA for instance). This would not leave any margin for problems such as a stalled servo. You should not take chances and when A4 flashes V.LO message you should put the battery on "A" fast charger and continue flying after "A" switches to trickle.

Please note that charge accepted by nicad and nimh batteries cannot be determined from battery voltage. This can only be determined by discharging the battery on a cycler and noting the capacity in mah.

Determining number of cells in a battery pack.
The "V" device can also be used for determining a number of cells in a correctly functioning battery pack. The procedure is as follows:
-Connect battery pack to a port and program "V" device on that port.
-Press and HOLD "RUN" key until battery voltage stops rising rapidly but hold for
at least one minute.
-Release the "RUN" key and quickly read the load voltage. If the load voltage drops rapidly repeat the procedure above. This time however hold the "RUN" key longer.
-Divide the load voltage reading by 1.2. Round off the resulting number to nearest whole number.
Example:
4.33 is rounded to 4
3.87 is rounded to 4
3.45 is rounded to 3.
-The resulting number represents number of cells in the pack provided however that there are no shorted cells in the pack.

Return to FAQ index

1.2

WHY MUST ALPHA4 BE CONNECTED DIRECTLY TO THE BATTERY?

Many TX's use diode in series with internal battery to prevent discharging of the battery through the TX charging jack. This is done so that the TX battery cannot be accidentally shorted through the charging jack and also to prevent damage from chargers that do not have proper polarity. There are more sophisticated methods to accomplish this protection but diode only costs a few cents so it is used.
Diode conducts current only in one direction and it has a temperature dependant voltage drop accros it. For this reason it will prevent any cycler from discharging the TX battery. Also it will prevent sophisticated unit such as Alpha4 from operating correctly in the charge modes.
A4 needs to measure battery voltage very accurately at all times in all modes of operation in order to follow battery voltage curve and correctly and precisely switch to trickle. For this reason it must be connected to the battery directly and not through a diode. If there is a diode in series with the TX charging jack A4 will display "OPEN" message as it cannot properly read voltage backwards through the diode. In this case you can bring leads directly from the battery to a separate connector on the back of the Tx or in some cases simply remove the battery and then connect leads directly to it.
It is also possible in some cases to bypass the diode with a fuse but you should consult the TX manufacturer before doing it.

Since cycling batteries is now a universally accepted practice one would think that TX manufacturers would correct this design problem. We suggest that you complain to these manufacturers about this situation.

Return to FAQ index

1.3

WHAT TO DO IF YOU DO NOT KNOW CAPACITY OF YOUR BATTERY

If you do not know a battery 's capacity, charge it first on "A" charger ( it does not ask for the capacity) and leave it on trickle for 3 hours. Next cycle it on "S" cycler. Enter capacity of 1000mah when requested. The "S" cycler uses peak detector for recharging and termination to trickle, so it does not matter if your guess of 1000 mah is not correct. When "S" completes discharge cycle and switches to "F"(FAST) the true capacity will be displayed. If you now wish to measure maximum possible capacity, charge the battery on "I" charger and after the charger switches to trickle leave it on trickle for several hours. Next cycle the battery on "C" cycler. The charge acceptance of battery is higher at the slower charge rate of "I" charger and leaving it for several hours on trickle puts small additional charge into the battery.

Please note that charge accepted by nicad and nimh batteries cannot be determined from battery voltage. This can only be determined by discharging the battery on a cycler and noting the capacity in mah.

Return to FAQ index

1.4

WHAT TO DO IF YOU OBTAIN "V.LO" MESSAGE ON ANY OF THE DEVICES.

The V.LO message means that the battery voltage is below normal. This condition can be caused by a battery that is excessively discharged or a battery with defective separator in one or more of the cells. In critical application such as model aircraft we wish to be aware that a separator failure is developing. Ignoring this condition will lead to eventual total failure of the battery and crash of the aircraft. This is why A4 will not allow you to process a battery that exhibits V.LO message. If V.LO message occurs the battery should be connected to a port programmed with "V" device. Next "R" (RUN) key should be depressed and HELD. When "R" key is depressed and held the load is removed and 1000mA quick charge is substituted as long as the "R" (RUN) key is held. The second four digit reading now represents the battery voltage under charge rather than under load. This reading should be carefully observed. If this voltage reading increases quickly over 1.2 Volts per cell then the battery is probably OK. If the voltage reading hesitates to increase above 1.2 volts per cell the battery is defective.

If the battery appears OK, hold the "R" (RUN) key for another 30 to 60 seconds and then press "P" key and reprogram the port to desired device or simply switch the battery to a port that has been previously programmed with the desired device.

Return to FAQ index

1.5

UNDER WHAT CONDITIONS SHOULD 18 GAUGE 36 INCH ADAPTER CABLE BE USED?

If the adapter cable is used for charging and cycling batteries from 2 to 12 cells the length and gauge of cable is not critical.

Only 18 gauge or heavier and 36 inches or shorter cable should be used with "V" device. This is necessary because the second four digit reading of the "V" device is taken under heavy 1000mA load and thin long cables will have a large voltage drop. This will result in voltage at the battery being higher than at the Alpha4 port jack. This will cause flashing V.LO message to appear at a higher battery voltage prompting you to charge battery more often than necessary.

If single cell is being discharged on one of the A4 cyclers a short heavy well connected cable must be used or discharge current regulation will not be maintained and capacity reading will be higher than normal. If the combined voltage drop across the connectors and the cable is higher than 0.1 Volt the constant current discharge will not be held.
Since this will result in lower than rated discharge current it will cause the capacity reading to be higher than normal. This does not apply to batteries consisting of 2 to 12 cells. For charging 1 to 12 cells cable and connector voltage drop is not critical.

Return to FAQ index

1.6

CAN I CHARGE AND CYCLE RAYOVAC RENEWAL CELLS ON THE ALPHA4?

These cells must be charged individually and not in packs. Also they require different cutoff voltage than either nicads or wet and gel cells. Their internal resistance is much higher than nicads. The short circuit current of individual cells is about 6 to 8 Amps and rapidly drops with each recharge. The short circuit current of nicads of equivalent size is several times higher and is approximately constant over hundreds of cycles. For this reason the Renewal cells are not recommended for higher current drain applications. In RC applications they might be OK for TX's but marginal for RX packs. The airborne pack has potentially a drain of about 1000 mA per stalled servo plus small RX drain. (servo at rest has very small current drain, while servo actuating nonbinding load might have a drain of about 100 to 300 mA). A positive feature of these batteries is very small self discharge current and high capacity when new and when lightly loaded. We felt that it was not worthwhile to include special charger on the Alpha4 for these batteries especially since only one cell could be processed per port. Also cycling of these batteries would only cause premature loss of capacity. Furthermore Rayovac offers special chargers for these batteries starting at about $14.00.

Return to FAQ index

1.7

WHAT ALPHA4 DEVICES SHOULD I USE FOR CYCLING AND CHARGING NIMH BATTERIES?

Nimh batteries do not develop pronounced voltage peak as nicads do. For this
reason nimh batteries cannot be charged on "A" and "S" devices. These devices
terminate on the onset of negative slope of the voltage versus time curve. They are
therefore peak detectors.
The "I" and "C" devices terminate ahead of voltage peak on the zero slope portion
of the voltage versus time curve. These devices are therefore suitable for processing
nimh batteries.
The "F" and "R" devices are fast charge devices which begin to taper down at 80%
capacity. In theory they should work fine with nimh batteries provided however
that charging nimh batteries at rates above C/10 is recommended by the battery
manufacturer.
To be on the safe side you should use only "I" and "C" devices with nimh batteries.
Please note that nimh batteries have much higher internal resistance than nicad's.
For this reason we do not recommend batteries in the lower capacity range for use with airborne packs.
A stall current of a servo can be as high as 1000 mA. Under high air load or with binding
linkage a servo could stall. This might cause excessive nimh battery voltage drop and
system failure. Furthermore nimh batteries exhibit temperature dependent high self-
discharge rates, have lower longevity than nicads's and present safety issues. Finally, in comparison to newest nicad's, nimh batteries no longer offer significant energy density advantage.

Return to FAQ index

1.8

WILL REVERSE PULSING OR "BURP" CHARGING REJUVENATE MY BATTERY?

This "technique" involves periodically reversing current flow during the charging process. Since 1960 claims were made that this technique would rejuvenate batteries of varied chemistries. Attempts to market this technique to battery manufacturers failed as technical tests revealed that this technique had no beneficial effect on the batteries.
We have also conducted our own tests. The technique is trivial to implement. In case of Alpha4 it is costless as it involves insertion of a few commands into the EPROM. Unfortunately the technique is useless and potentially harmful. If the current reversals are at sufficiently slow rate and the duration of the reversal is sufficiently long the batteries under charge undergo in effect continuous shallow cycling and the battery capacity is prematurely decreased. At higher rates the effect is reduced. In any case no rejuvenation of any kind is observed. Claims that a "burp" charger will substitute for a battery cycler are simply false. A simple charger with couple of LED's on the front panel will not measure the capacity of your battery.
"Burp" charging is mainly used in situations where an attempt is being made to market an otherwise unsophisticated battery charger at an excessive price.

Return to FAQ index

1.9

WHY CAN CHARGERS USING TIMERS DAMAGE BATTERIES?

Most nicad and nimh batteries are designed to accept overcharge at C/10 rate or lower without immediate damage. C/10 current rate equals battery capacity divided by ten. If these batteries are overcharged above this rate then gas pressure buildup and venting will occur which will lead to premature loss of capacity. To obtain full service life, batteries should be switched to trickle when they are fully charged and not by a timer.
All unsophisticated cycler/chargers and some supposedly sophisticated cycler/chargers use timers to terminate to trickle. If the battery capacity divided by 10 is the same or less than the charger current rate no immediate damage will occur. Since most cycler/chargers have only a few current ranges the selection of proper current rate is often not possible. A higher current rate than C/10 is often selected leading to battery damage. If lower current range is selected the timer will switch to trickle before the battery is fully charged.
In some very high priced cycler/chargers a timed charge of as high as C/5 is used. This is totally unacceptable as it will lead to certain loss of capacity with most nicad and nimh batteries. These high priced cycler/chargers should use a slope following technique not timers for proper termination to trickle.

Alpha4 does not use timers for termination to trickle. Accurate analog to digital converters are used to measure battery voltage in all modes of operation. From these measurements Alpha4 calculates the slope of the voltage versus time curve of the battery.
"I" and "C" devices terminate to trickle in the zero slope region ahead of the peak at 95% capacity.
"A" and "S" devices terminate to trickle at the onset of negative slope at the peak at 100% capacity.
"F" and "R" devices begin to taper down at 80% capacity.

Return to FAQ index

2.0

USING "N" DEVICE WITH NEW NICADS.

New nicads should be left on "N" device for a couple of days before processing with other devices. This will properly "form" new batteries. The "N" device charges at C/10 rate and does not terminate to trickle. At the C/10 rate batteries will not be damaged or lose capacity over this short period of time.
New batteries often have been sitting on the shelf for a long time and due to self-discharge exhibit lower than normal voltage. If this is the case these batteries will generate "V.LO" message on all devices except the "V" device. Please see FAQ paragraph 1.4 above for instructions how to proceed in this case.

Return to FAQ index

2.1

WILL ALPHA4 CHARGE LITHIUM BATTERIES?

At the present time Alpha4 cannot process lithium rechargeable batteries. As the demand increases, and numerous technical issues are resolved we will consider firmware change for Alpha4 to accomodate these batteries. At this time it is totally impractical to implement this change for many of the following reasons.
Many of these batteries require battery specific charger. Standardization is a problem as some battery packs include internal circuitry. Need to monitor individual cells when cells are connected in series presents a problem. Inability to accept a fast charge at higher current rates limits their appeal. The maximum current available would also be of concern if one or two servos stall. With some of the battery types there are unresolved safety issues and the number of cycles available relative to cost is not competitive. On the other hand low weight per energy stored and low selfdischarge rate are big pluses.

Since the safety issue is of extreme importance in consumer applications the following is a review of rechargeable lithium technology from safety viewpoint.

-Lithium metal with liquid electrolyte. Highly reactive liquid lithium presents unacceptable safety hazard for consumer applications.

-Lithium metal with polymer electrolyte. Again presence of metalic lithium is a very serious safety hazard.

-Lithium ion with liquid electrolyte. Free flowing electrolyte is highly flammable.

-Lithium ion with solid polymer electrolyte. This is the safest technology and the only one recommended for consumer applications.

Safety warning:
Lithium in the metallic form is highly reactive. This presents difficulties in rechargeable
form. Repeated charge discharge cycles can cause electrode surface irregularities
called dendrites. These can penetrate the separator and form a short circuit between
the electrodes causing cell temperature to rise. If the temperature reaches the lithium
melting point severe flaming might result. For this reason this rechargeable technology
is unsuitable for consumer applications.

Return to FAQ index

2.2

IS MEASURING INPUT CAPACITY DURING CHARGING OF VALUE?

Unfortunately this measurment is almost useless as the input capacity is not the retained capacity. Due to both thermal and chemical inefficiencies batteries require 20 to 60 percent excess charge. For instance if you are charging 600 mah battery at 60 ma it might take up to 16 hours to obtain full charge. It will never take just 10 hours since this would require ideal battery which we do not have.
As the batteries age the internal resistance increases causing higher thermal loss and the excess charge must be increased. The above comments apply to fast charging as well. Since thermal losses are current squared multiplied by internal resistance of the battery the disparity between input and retained charge is even greater due to higher current during fast charging.

The thermal losses described above occur also during discharging. At higher discharge current the apparent capacity is smaller than at lower discharge current. The difference will depend again on internal resistance of the battery.

Input capacity measurment should never be used for fast charging at the field for two reasons:

1) The mah usage of the airborne system is not constant and depends on air loads and
and degree of binding in pushrods.

2) The input capacity is not the retained capacity as described above.

When used repetitevely this method will cause the errors to accumulate which will lead to inadequately charged battery and a crash.

To speed up charging between flights simply fly fewer times between charging.
Charging with Alpha4 "A" charger until it switches to trickle will assure fully charged battery and therefore large safety reserve for the next couple of flights. Use "V" device before each flight to check battery voltage as additional safety measure.

Return to FAQ index

2.3

WHAT FAST CHARGE CURRENTS ARE RECOMMENDED FOR FAST CHARGING TX AND RX.

The wiring and connectors in the RC radio system are not designed for use with very high currents. Currents in excess of 1000 ma should never be used as they will lead to equipment damage and/or loss of warranty coverage.
To speed up charging between groups of flights simply fly fewer times between charging.
Use Alpha4 "A" charger until it switches to trickle. After only two or three flights this should not take very long. Use "V" device before each flight to check battery voltage under load.
Unlike other peak detectors Alpha4 contains a sophisticated slope detection capability which will not cause batteries to become hot and overcharge.
There are numerous special purpose, high current peak detector chargers available for very fast field charging of electric car and electric airplane motor batteries. In these applications the concerns are winning races and flight duration and not flight safety and battery life. Alpha4 is not addressing this market and should not be compared with these special purpose chargers. Fast charging is only one of Alpha4's many capabilities.


Return to FAQ index

2.4

ADDITIONAL INFORMATION ABOUT USE OF ALPHA4 "I", "A" AND "V" DEVICES.

Charge acceptance of batteries is higher at low current charge rates so use "I" charger and leave for couple hours on trickle when time allows.
"I" charger should also be used in the above manner when testing subsequently with "C" cycler for maximum battery capacity. Please note that "I" charger terminates to trickle based on battery state of charge and not a timer. At lower current rates this is difficult to accomplish since it requires very accurate measurement system. To our knowledge Alpha4 is the only unit with this capability.
At the field use "A" charger, monitor with "V" device before each flight and charge as necessary. If charging is done after couple of flights it will not take very long to fill the battery. You can also use the "F" charger at the field but read the manual, section "Programming Fast Charger, Trickle" first.
Conservative battery capacity rating would be at the one hour discharge rate. If you wish to duplicate this condition use discharge current closest to the battery capacity. For instance for 600 mah battery use 500 ma discharge rate (two ports programmed).
There is no harm using lower or higher discharge current but at the lower current rate the measured capacity will be somewhat greater than at higher current rate due to lower thermal losses. These thermal losses are proportional to battery internal resistance.

Please note that charge accepted by nicad and nimh batteries cannot be determined from battery voltage. This can only be determined by discharging the battery on a cycler and noting the capacity in mah.

Return to FAQ index

2.5

ABOUT CHARGING WET AND GEL CELLS

Wet and gel batteries require special charging methods to deliver full service life. Simple chargers nearly always subject these batteries to overcharge. During overcharge the electrical energy rather than being stored in the battery is used instead for breaking down the battery electrolyte into hydrogen and oxygen (gassing). This causes the battery to dry out and lose capacity. If wet or gel cells are left partially or completely discharged or are simply allowed to self-discharge, a lead sulfate compound is formed on the plates. This compound hardens over time and cannot be converted by subsequent charging. The battery loses capacity and is said to be sulfated.

To address the above problems a special charger is required. This charger first charges the battery to 100% and then switches to float mode. In float mode the charger supplies only enough current to neutralize self-discharge.
The "W" device of Alpha4 delivers these functions with total flexibility for wet and gel batteries from 1 through 9 cells at 2 Volts per cell. It will handle capacities from 10mAh to very large 1000 Amp/hours. Typical automobile battery has a capacity of 60Ah.
The "FAST" charge rate is 1000mA divided by the number of programmed ports. To obtain maximum charge rate of 1000mA program only one port. The "FLT" (float) charge rate varies with the type of battery and could be under 1mA for small batteries. Expect a 6Amp/hour gel cell to remain on "FAST" for at least 6 hours if completely discharged. Automobile batteries may stay on "FAST" for several days.

The "W" device is equipped with a 4 digit DVM. Expect the DVM to reach well above 14V for 6 cell 12V wet or gel cell before switching to "FLT". Expect the "FLT" voltage to stabilize around 13.30V. Exact voltage depends on battery. Do not expect the "W" device to operate properly with batteries that are aged, sulfated, dried out, open or shorted. It will not rejuvenate worn out batteries. Dried out batteries will go to "FLT" prematurely and not accept full charge. Batteries with partially or fully shorted cells may never go to "FLT".
The "W" device is intended for fresh batteries. If you experince incorrect operation with "W" device obtain a fresh battery. With fresh batteries "W" device will deliver a full service life of about 400 cycles.

Return to FAQ index

2.6

TESTING ADAPTER CABLES WITH ALPHA4.

Adapter cables can be tested for lack of contnuity, short circuits and intermittent connections with any of the Alpha4 devices.

IT IS VERY IMPORTANT TO TEST THE ADAPTER CABLE AND ITS CONNECTOR FOR SHORT CIRCUIT BEFORE PLUGGING IN THE BATTERY.

IF THERE IS A SHORT CIRCUIT BATTERY LEADS COULD MELT AND THE BATTERY WILL BE DAMAGED. EQUIPMENT HOUSING THE BATTERY SUCH AS PLASTIC TRANSMITTER CASES WILL BE DAMAGED.

YOU SHOULD TEST ADAPTER CABLES YOU MAKE AS WELL AS CABLES PURCHASED COMMERCIALLY.

ALPHA4 CANNOT SUPPLY SUFFICIENT CURRENT TO CAUSE SUCH
DAMAGE. BATTERIES ON THE OTHER HAND CAN SUPPLY VERY HIGH
CURRENT INTO A SHORT CIRCUIT.

If the leads to your battery pack have melted and /or heat shrink wrap of your battery pack has split due to excessive heat do not send Alpha4 for repair.
Check your cables, plugs and connectors for short circuit using the procedure outlined below. Please note that the short circuit could be intermittent.

Alpha4 has the following diagnostic error messages:

"OPEN"
"SHORT"
"REVER" (reverse polarity)
"V.LO" (voltage too low)
"V.HI" (voltage too high)

Of the above five messages only the first two message will be used for testing adapter cables and connectors.

TESTING PROCEDURE

Program "V" (simplest to program) device on port 1 and insert the adapter cable to be tested into the port 1 jack.

If there is no short circuit in the adapter cable "OPEN" message will remain on the screen. Bend conductors back and forth at the connector of the adapter cable to make certain that there are no intermittent short circuits.

If there is a short circuit in the cable or its connector a "SHORT" message will appear on the screen. Correct the short circuit before plugging any batteries into the adapter cable or meltdown will occur.

When "OPEN" stays on it is safe to plug in the battery into the adapter cable. The "OPEN" message must now disappear (and voltage reading appear) if the cable and connectors have continuity. Bend cable back and forth at both connectors to make certain that there is no intermittent continuity. "OPEN" message should not show.

If "OPEN" message stays on or shows intermittently the cable and/or connector have no continuity and must be repaired.

Return to FAQ index

2.7

WILL CONTINUOUS TRICKLE CHARGING HURT BATTERIES?

Battery manufacturers offer specifications for battery longevity as related to continuous charge current. At C/50 continuous trickle charge the battery longevity would be considerably higher than at C/10 continuous charge but slightly lower than if battery was not continuously trickle charged.
For instance if battery longevity would be 5 years with continuous trickle charge you could expect 5.5 years if battery was not continuously trickle charged.
More important than small loss of capacity might be the fact that continuous trickle charging might mask partial shorts developing in the separator in one or more of the cells. To test for partial shorts charge the battery fully on "I" charger and then remove it from the charger and do not use it for 10 days. Next put the battery on "C" cycler and measure the remaining capacity. If the battery is down more than 10 percent due to self discharge the separator might be suspect.

Return to FAQ index

2.8

BATTERY CAPACITY MEASUREMENTS

Battery capacity measurements depend on many factors and exact capacity rating as written on a cell cannot normally be exactly duplicated.

The measured capacity will depend to certain extent on the discharge rate. At lower current rate ( more ports programmed ) the measured capacity will be greater than at higher rate because of lower thermal losses due to battery internal resistance.
You should find out at what discharge rate your battery was specified
(1C rate, C/2 rate or C/5 rate) and then discharge close to that rate.
Please note that most Sanyo batteries are conservatively rated and have higher capacity than specified.

Charging at a slower C/10 rate on "I" charger will result in higher charge acceptance than fast charging on "A" charger. Leaving battery on trickle charge for a few hours will result in still higher charge acceptance.

In the discharge mode Alpha4 interrupts discharge current for a few milliseconds and samples voltage readings at no load. The discharge is terminated at 1.00 Volt per cell. This makes the cutoff point independent of connector and wire resistance and results in a deep discharge without cell reversal producing higher capacity reading . Other cyclers terminate discharge at 1.1 Volts with discharge current on. This results in unreliable shallow discharge with capacity readings lower than actual battery capacity and influenced by connector and wire resistance.

Frequency of cycling.

To verify capacity batteries should be cycled every month or perhaps every two months. Since batteries are guaranteed only for 500 to 1000 cycles frequent cycling is counterproductive as it tends to reduce the battery capacity.

Determination of capacity use per flight.

To determine capacity use per flight follow this procedure:

1)
Charge the battery on the "I" charger and leave it on trickle for at least 3 hours.

2)
Cycle the battery on "C" cycler. Leave the battery on "C" cycler until Alpha4 switches to trickle. Leave on trickle for at least 3 hours.

3)
Write down the capacity indicated on "C" cycler. This is the maximum capacity for this battery.

4)
Fly the aircraft with this battery and count the number of flights.

5)
Cycle the battery on "C" cycler without first charging. Write down the remaining capacity.

6)
Subtract the remaining capacity in step 5 above from maximum capacity in step 3 above and divide the result by the number of flights. This is your average usage in mah per flight. This applies only to this aircraft. Other aircraft will have different capacity usage per flight.

Return to FAQ index

2.9

SURFACE CHARGE VS ACCEPTED CHARGE

Please note that charge accepted by the battery cannot be determined by measuring voltage after charging. Voltage right after charging is higher than normal due to surface charge. This voltage due to surface charge decreases with time. It rapidly decreases with discharge.

The higher voltage due to surface charge is generally meaningless
except that an unusually high voltage after charge normally indicates poor quality or dried out battery.

To correctly determine charge accepted by the battery, charge the battery first and next cycle it.

On Alpha4 follow this procedure:

1)
Charge the battery on "I" charger, leave it on trickle for couple of hours.

2)
Cycle the battery on "C" cycler. Set the discharge rate as close as possible to the battery capacity. For instance if the battery capacity
is 1000 mah program only one port to set the current discharge rate to 1000 ma. If you wish to insert minimum charge after discharge, program the "C" cycler with the capacity of 0010. This will reduce the charge current after discharge to 1 ma which will insert minimum charge into the battery.

3)
Write down the capacity after discharge is completed. This is the charge accepted by the battery.

Return to FAQ index


Go to Alpha4 index page
.

.

.

.